Compact substations · Outdoor rated
Transformer, switchgear, and LV panel, factory-built and ready to commission.
Our package substation range delivers a complete medium to low voltage step-down solution in a single outdoor-rated enclosure. Transformer up to 3 MVA, MV switchgear (air or SF6 RMU), and LV distribution, designed, assembled, and tested in Madinah. Site work is limited to cable connection.
- Voltage
- Up to 36 kV primary
- Transformer power
- Up to 3 MVA
- Secondary voltage
- 230 / 400 / 690 V
- Protection
- IP 54 · forced or natural
The range
Three configurations engineered for different deployment scenarios.
From the standard 24 kV reference build to smart-ready Vision 2030 megaproject configurations and 36 kV heavy-duty variants.
- Up to 24 kV · Standard01 / 3
Package substation, standard
The reference configuration. Transformer compartment, MV compartment (air or SF6 RMU), and LV distribution in a single outdoor-rated enclosure. RAL 7033 finish, IP 54, natural or forced cooling.
Up to 24 kV · 50 kVA to 3 MVA · 50 kVrms · 125 kVpeak · IP 54
- Up to 24 kV · Smart-ready02 / 3
Package substation, smart
Vision 2030 ready
Standard configuration upgraded with smart infrastructure. Transformer condition monitoring, partial discharge detection, and SCADA integration over IEC 61850 or Modbus.
Standard specs + IEC 61850 · Temperature monitoring · PD detection · Energy metering
- Up to 36 kV · Heavy-duty03 / 3
Package substation, 36 kV
Engineered for 36 kV primary voltage. Specified for transmission-adjacent applications, large industrial sites, and utility distribution where higher primary voltage is required.
Up to 36 kV · Up to 3 MVA · 70 kVrms · 170 kVpeak · IP 54
Side-by-side specifications
Full technical comparison across the substation range.
| Specification | Standard | Smart | 36 kV |
|---|---|---|---|
| Rated voltage | Up to 24 kV | Up to 24 kV | Up to 36 kV |
| Transformer power | 50 kVA to 3 MVA | 50 kVA to 3 MVA | Up to 3 MVA |
| Rated frequency | 50 / 60 Hz | 50 / 60 Hz | 50 / 60 Hz |
| Power frequency test | 50 kVrms | 50 kVrms | 70 kVrms |
| Impulse withstand | 125 kVpeak | 125 kVpeak | 170 kVpeak |
| Secondary voltage | 230 / 400 / 690 V | 230 / 400 / 690 V | 230 / 400 / 690 V |
| MV switch current | 630 A | 630 A | 630 A |
| Cooling | Natural / forced | Natural / forced | Natural / forced |
| Standard colour | RAL 7033 | RAL 7033 | RAL 7033 |
| Degree of protection | IP 54 | IP 54 | IP 54 |
| Smart infrastructure | Optional | Supported | Optional |
| Remote monitoring | Optional | Supported | Optional |
| IEC 61850 ready | Optional | Supported | Optional |
Standard
- Rated voltage
- Up to 24 kV
- Transformer power
- 50 kVA to 3 MVA
- Rated frequency
- 50 / 60 Hz
- Power frequency test
- 50 kVrms
- Impulse withstand
- 125 kVpeak
- Secondary voltage
- 230 / 400 / 690 V
- MV switch current
- 630 A
- Cooling
- Natural / forced
- Standard colour
- RAL 7033
- Degree of protection
- IP 54
- Smart infrastructure
- Optional
- Remote monitoring
- Optional
- IEC 61850 ready
- Optional
Smart
- Rated voltage
- Up to 24 kV
- Transformer power
- 50 kVA to 3 MVA
- Rated frequency
- 50 / 60 Hz
- Power frequency test
- 50 kVrms
- Impulse withstand
- 125 kVpeak
- Secondary voltage
- 230 / 400 / 690 V
- MV switch current
- 630 A
- Cooling
- Natural / forced
- Standard colour
- RAL 7033
- Degree of protection
- IP 54
- Smart infrastructure
- Supported
- Remote monitoring
- Supported
- IEC 61850 ready
- Supported
36 kV
- Rated voltage
- Up to 36 kV
- Transformer power
- Up to 3 MVA
- Rated frequency
- 50 / 60 Hz
- Power frequency test
- 70 kVrms
- Impulse withstand
- 170 kVpeak
- Secondary voltage
- 230 / 400 / 690 V
- MV switch current
- 630 A
- Cooling
- Natural / forced
- Standard colour
- RAL 7033
- Degree of protection
- IP 54
- Smart infrastructure
- Optional
- Remote monitoring
- Optional
- IEC 61850 ready
- Optional
Where it's deployed
Rapid-deployment power for the projects that define the Saudi skyline.
Factory-built and outdoor-rated means site work is limited to cable connection. Package substations are specified wherever deployment speed, repeatability, and uniform quality matter more than a brick-built footprint.
- 01
Vision 2030 megaprojects
NEOM, the Red Sea Project, Qiddiya, and other giga-projects requiring rapid, repeatable power infrastructure deployment. Smart configurations integrate with project-wide SCADA.
- 02
Renewable energy plants
Solar PV plants requiring distributed step-down substations across large land areas. The smart configuration enables remote monitoring of dozens of substations from one control room.
- 03
Urban distribution networks
Saudi Electricity Company distribution expansion. Package substations replace traditional brick-built substations for faster deployment and consistent quality.
- 04
Real-estate developments
Master-planned residential and mixed-use communities. Single-supply package substations serve as the development's electrical backbone.
- 05
Industrial sites
Heavy industry, manufacturing complexes, and logistics hubs requiring high-quality step-down power at multiple locations across a campus.
- 06
Infrastructure projects
Airports, ports, metro systems, and highway corridors. Applications where on-site assembly time is constrained and reliability is non-negotiable.
Four package substations tapped off a single 33 kV feeder, each feeding a local load. The deployment shape that Vision 2030 megaprojects, solar plants, and SEC urban networks share.
Engineered to standard
Type-tested. Site-ready. Smart-capable.
The package substation family is designed and type-tested against the IEC and DIN switchgear series, with the certifications a Saudi industrial buyer expects.
IEC and DIN standards compliance
- IEC 62271-100HV AC circuit-breakers.
- IEC 62271-102HV AC disconnectors and earthing switches.
- IEC 62271-103Switches above 1 kV up to 52 kV.
- IEC 62271-105AC switch-fuse combinations.
- IEC 62271-200AC metal-enclosed switchgear up to 52 kV.
- DIN VDE 0670 / 0671German standards for European compatibility.
Management systems and protocols
- ISO 9001 : 2015
- ISO 14001 : 2015
- ISO 45001 : 2018
- IEC 61850 · Smart configuration
Documentation
Everything your engineering team needs to specify, install, and commission.
Datasheets, dimensional drawings, type-test certificates, and installation manuals, released on engagement to the named project team.
Family datasheet
PDF · ~7 MB
All three configurations, full specifications, and single-line diagrams.
Request copy
Dimensional drawings
PDF + DWG · ~11 MB
CAD-ready drawings including foundation requirements and cable entry layouts.
Request copy
Type-test certificates
PDF · ~6 MB
Independent type-test certificates per the IEC 62271 series.
Request copy
Installation manual
PDF · ~5 MB
Foundation requirements, lifting procedures, cable connection, and commissioning.
Request copy
Package substation documentation is released under non-disclosure to qualified buyers. Send your project reference and we will return the bundle within one working day.
Often deployed together
Related products in the TEPCO portfolio.
The families most often specified alongside package substations on Saudi distribution projects.
Primary distribution
Medium voltage switchgear
Primary distribution upstream of package substations in larger network hierarchies.
View MV switchgear
Component
Ring main units
The MV switching component inside a package substation. Available in air, AIS, or GIS configurations.
View RMU family
Digital
Smart grid and automation
Add full IEC 61850 integration to any substation for SCADA-level monitoring and protection.
View smart grid
Ready to specify package substations?
Send us your project requirements or single-line diagram. Our Madinah engineering team will respond within 24 hours.